Footing Size Calculator

Determine isolated footing dimensions based on column loads and soil bearing capacity. Calculate concrete volume, reinforcement requirements, and check bearing pressure.

Column Details

Unfactored axial load from column

Soil Conditions

Moderate density - Allowable: 200 kN/m²

From geotechnical report (overrides soil type)

Material Properties

Enter column load and soil properties to size footing

Notes:

  • Punching check per EN 1992-1-1 cl. 6.4 (simplified, concentric load); allowable bearing values are indicative presumed values
  • Square footing assumed for isolated foundations
  • Punching shear at basic control perimeter 2d from column face, soil reaction inside the perimeter deducted
  • Groundwater may reduce effective bearing capacity
  • Verify soil parameters with geotechnical investigation
Send This Calculation to Arkan
Share your inputs and results with our team, along with your contact details, if you'd like to discuss them or see how Arkan handles this work.

IMPORTANT DISCLAIMER

This calculator provides PRELIMINARY ESTIMATES ONLY and is intended for planning and budgeting purposes. Results should NOT be used for final structural design or construction without verification by a licensed Professional Engineer (PE) or Chartered Engineer (CEng).

By using this tool, you acknowledge that:

1. All calculations are indicative and may not account for site-specific conditions, load combinations, or local code requirements.

About This Calculator

The Footing Size Calculator helps structural and geotechnical engineers design isolated footings for columns across UAE and Gulf construction projects. Calculate footing dimensions based on column loads and allowable soil bearing capacity, with concrete volume and reinforcement requirements. Essential for foundation design in high-rise towers, villas, and commercial buildings where soil conditions vary significantly.

When to Use This Calculator

  • Designing isolated footings for column foundations
  • Checking bearing pressure against soil capacity
  • Estimating concrete and rebar for foundation BOQ
  • Preliminary foundation sizing for tender estimates
  • Verifying footing adequacy for increased loads

How to Use This Calculator

1

Enter Column Load

Input axial load from column in kN (from load takedown calculation).

2

Specify Soil Capacity

Enter allowable bearing capacity from geotechnical report (kN/m² or kPa).

3

Set Footing Depth

Input footing thickness (minimum 300mm for structural adequacy).

4

Add Eccentricity

If applicable, enter moment or eccentricity affecting pressure distribution.

5

Calculate Results

Get footing dimensions, bearing pressure, concrete volume, and rebar requirements.

Typical Scenarios in UAE & Gulf Projects

Villa Foundation in Dubai

A 300×300mm villa column carries 800 kN (service) on medium clay (150 kPa presumed). With a 400mm thick C30 footing the calculator gives a 2.5m × 2.5m base (2.5 m³ concrete), 128 kPa bearing pressure, and a punching check of 0.44 MPa against 0.50 MPa (EN 1992-1-1). Reinforcement is indicative and must be designed by the engineer.

Tower Footing in Abu Dhabi

A 1.0m square column delivers 12,000 kN to rock with 300 kPa allowable bearing. The calculator gives a 6.7m × 6.7m base. At 1.0m thick the punching check fails (0.66 MPa against 0.39 MPa); at 1.5m it passes (67 m³ concrete). A footing this size needs full design by a structural engineer, and piles or a raft may be more economical.

Frequently Asked Questions

Required area = Column load ÷ Allowable bearing capacity. For 1000 kN load on 200 kPa soil: Area = 1000/200 = 5m². Use square footing √5 = 2.24m, round to 2.3m × 2.3m. Check actual pressure is below allowable. Add depth for punching shear and bending capacity.

Typical UAE/Gulf bearing capacities: Loose sand 50-100 kPa, Medium dense sand 100-200 kPa, Dense sand 200-400 kPa, Weak rock 300-500 kPa, Strong rock 500-2000+ kPa. Dubai Marina area typically 150-250 kPa. Always use site-specific geotechnical report values.

Minimum footing thickness: 300mm for light loads, 400-500mm typical for buildings, 600-1000mm for heavy column loads. Thickness governed by: Punching shear around column, One-way shear at d from column face, Bending moment at column face, Development length for reinforcement. Increase for high loads or weak concrete.

Take Your Calculations Further

This calculator reflects the logic built into Arkan's construction management platform.

Last Updated: January 2026

Standards Reference: Punching check per BS EN 1992-1-1 cl. 6.4 (simplified); presumed bearing values are indicative only

Need More Than Calculators?

Arkan brings all your construction management together: BOQ tracking, payment certificates, document management, scheduling, and more. All integrated. All in one place.