العربية

Cable Size Calculator: Cable Sizing for Current and Voltage Drop

Determine appropriate cable sizes based on load current, voltage drop limits, and installation conditions. Includes IEC derating factors for temperature, grouping, and installation methods.

Last updated: January 2026

Units
Load Parameters
Installation Conditions

Enter load parameters and click Calculate to see cable sizing results

Notes:

  • Calculations based on IEC 60364 / BS 7671 standards
  • BS 7671 guidance (public LV supply): total voltage drop from origin 3% for lighting, 5% for other uses; check the current DEWA/ADDC regulations and project specification
  • XLPE insulation allows higher operating temperature
  • Always verify with local electrical codes and regulations
  • Consider future load growth when selecting cable sizes
Your results
Email me this calculation
Leave your email and phone number and the Arkan team will send you this calculation. The calculator stays free and needs no sign-up.

We use your email and phone number to send this calculation and follow up on it. See our Privacy Policy.

DISCLAIMER

This calculator provides ESTIMATES for preliminary planning purposes. Results are based on standard assumptions and may not reflect your specific project conditions.

By using this tool, you acknowledge that:

1. All calculations are approximate and based on typical industry standards and assumptions.

Embed this calculator on your site

Paste this snippet into your page. The embedded calculator is free to use and links back to this page.

About This Calculator

The Cable Sizing Calculator helps electrical engineers and MEP contractors determine the correct cable cross-section for power distribution systems across the UAE and Gulf. Calculate required cable sizes based on load current, voltage drop limits, cable length, and installation conditions. Applies IEC/BS derating factors for ambient temperature, cable grouping, and installation methods commonly used in Gulf construction.

Formula

Design current Ib (three-phase) = P × 1,000 ÷ (√3 × U × power factor)

Design current Ib (single-phase) = P × 1,000 ÷ (U × power factor), or enter the current directly

Total derating factor k = installation factor × temperature factor × grouping factor

Required base capacity = Ib ÷ k; choose the smallest size in the table whose base capacity is at least that value

Voltage drop (V) = mV/A/m × Ib × length ÷ 1,000

Voltage drop (%) = voltage drop (V) ÷ U × 100. If it exceeds your limit, the next larger size that satisfies both capacity and voltage drop is selected

Derated capacity Iz = base capacity of the selected size × k

Suggested breaker In = smallest standard rating with Ib ≤ In ≤ Iz

Worked example

10 kW three-phase load, 50 m run on a perforated tray

Inputs

  • Load: 10 kW at power factor 0.85, 400 V three-phase
  • Cable length: 50 m; maximum voltage drop: 3%
  • Installation method E (perforated tray), ambient 35 °C, 1 circuit, PVC (70 °C)

Steps

  1. Ib = 10,000 ÷ (√3 × 400 × 0.85) = 17 A (16.98 A)
  2. k = 1.00 × 0.94 × 1.00 = 0.94; required base capacity = 16.98 ÷ 0.94 = 18.1 A
  3. Capacity alone would select 2.5 mm² (21 A)
  4. Voltage drop at 2.5 mm² = 15 mV/A/m × 16.98 × 50 ÷ 1,000 = 12.7 V = 3.18%, above the 3% limit
  5. Next size, 4 mm² (28 A base): 9.5 × 16.98 × 50 ÷ 1,000 = 8.07 V = 2.02%, within the limit
  6. Iz = 28 × 0.94 = 26.3 A; smallest standard breaker with 17 A ≤ In ≤ 26.3 A is 20 A

Result: 4 mm² cable, 2.02% voltage drop, derated capacity 26.3 A, suggested breaker 20 A

Assumptions and limits

  • Current-carrying capacities and mV/A/m values come from one built-in table of typical copper-conductor values. The same table is used for PVC and XLPE; insulation type only changes the temperature factor.
  • The three-phase result uses the three-phase column of the table and the single-phase result uses the single-phase column. Only 230 V single-phase, 400 V and 415 V three-phase are modelled.
  • Derating factors for installation method, ambient temperature and grouping are simplified; the nearest tabulated temperature and grouping value is used.
  • Short-circuit withstand, earth-fault loop impedance, harmonics, motor starting and cable-specific manufacturer data are not checked.
  • Voltage drop limits and cable selection rules differ between the governing code, the utility (such as DEWA or ADDC) and the project specification: check the governing code and project specification. Final design should be reviewed by a qualified electrical engineer.

When to Use This Calculator

  • Designing electrical distribution systems for buildings
  • Sizing main feeders and sub-main cables
  • Checking voltage drop compliance for long cable runs
  • Applying derating factors for Gulf climate conditions
  • Verifying cable specifications for tender submissions

How to Use This Calculator

1

Enter Load Details

Input load current (A), voltage (V), and power factor for the circuit.

2

Specify Cable Route

Enter cable length and select installation method (tray, conduit, direct burial, etc.).

3

Set Derating Factors

Apply factors for ambient temperature, cable grouping, and installation conditions.

4

Check Voltage Drop

Verify voltage drop is within the limit set by the wiring standard or specification you follow.

5

Review Cable Size

Get recommended cable cross-section (mm²) with current-carrying capacity verification.

Typical Scenarios in UAE & Gulf Projects

Commercial Tower in Dubai

An MEP contractor checks the main feeder for an 800A load. The calculator flags that 800A exceeds the largest single cable in its table (300mm²) and gives no breaker size: the feeder needs parallel cables or a busbar trunking system designed by an electrical engineer.

Industrial Facility in Abu Dhabi

A 200A three-phase motor feeder (80m, XLPE, direct in ground, 45°C, 3 grouped circuits). Combined derating is about 0.55, so the calculator selects 300mm² (216A derated) with 0.5% voltage drop and a 200A breaker (Ib ≤ In ≤ Iz).

Calculation Methodology

How Cable Sizing Works

Cable sizing ensures the selected conductor can safely carry the design current without overheating or exceeding voltage drop limits. The fundamental requirement is Iz ≥ Ib ÷ (Ca × Cg × Ci), where Iz is the cable's tabulated current rating, Ib is the design current, and Ca, Cg, Ci are derating factors for ambient temperature, cable grouping, and installation method respectively. The calculator selects the smallest standard cable size (from 1.5 mm² to 300 mm²) whose derated capacity meets or exceeds the design current.

Voltage Drop Calculation

After selecting a cable for current capacity, the voltage drop must be verified. The formula is: Vd(%) = (mV/A/m × Ib × L) ÷ (1000 × V) × 100, where mV/A/m is the cable's voltage drop per ampere per metre (from IEC tables), Ib is the design current in amps, L is the one-way cable length in metres, and V is the system voltage. Voltage drop limits come from the governing regulation and project specification (BS 7671 and IEC 60364-5-52 give guidance of 3% for lighting and 5% for other uses; check the current DEWA or ADDC/ADWEA rules). If the drop exceeds limits, the calculator automatically upsizes the cable.

Understanding Derating Factors for Gulf Conditions

Standard cable ratings assume 30°C ambient temperature, a single circuit, and open installation. Gulf construction rarely matches these ideal conditions. The ambient temperature factor (Ca) reduces capacity for the 40–50°C temperatures common in UAE — for example, a PVC cable at 45°C is derated to 79% of its standard rating. The grouping factor (Cg) accounts for reduced heat dissipation when multiple cables share a tray or conduit — three grouped cables retain only 70% of individual capacity. The installation method factor (Ci) reflects whether the cable is clipped to a surface (factor 1.0), in conduit (0.87), or buried in a duct (0.80). All three factors multiply together to determine the effective current-carrying capacity.

Frequently Asked Questions

What is the maximum voltage drop allowed in UAE?

BS 7671 (Appendix 4) and IEC 60364-5-52 give guidance for installations supplied from a public low-voltage network: a total voltage drop from the origin of the installation to the point of use of no more than 3% for lighting and 5% for other uses (6% and 8% where the installation has its own private LV supply). How that total is split between feeders, sub-mains and final circuits is a design choice. Check the current DEWA or ADDC/ADWEA regulations and the project specification, which may set their own limits.

How do you calculate cable derating for high ambient temperature?

Standard cable ratings are at 30°C ambient. For Gulf conditions (40-50°C), apply derating factors: at 40°C = 0.87, at 45°C = 0.79, at 50°C = 0.71. Example: A 95mm² cable rated 200A at 30°C becomes 174A at 40°C (200 × 0.87).

When should I use aluminum cables instead of copper?

Aluminum cables are cost-effective for larger sizes (>50mm²) and long runs. Common in main feeders and outdoor installations. Requires larger cross-section than copper (typically 1.6× area for same current). Use copper for final circuits, motor connections, and where space is limited.

What cable size do I need for a 32A circuit?

For a 32A circuit at 30°C with PVC insulation clipped direct (Method C): 4mm² copper cable is rated at 36A, sufficient for 32A. However, if the cable is in conduit (Method B1, rated 30A at 4mm²), you need to upsize to 6mm² (rated 38A). Always check derating for ambient temperature — in UAE at 40°C, 4mm² drops to ~31A, which is marginal for 32A. A 6mm² cable is the safer choice for Gulf conditions.

How do I calculate voltage drop for a 3-phase cable?

For three-phase circuits, voltage drop is: Vd(%) = (mV/A/m × Ib × L) ÷ (1000 × VL) × 100, where VL is the line-to-line voltage (e.g., 400V). The mV/A/m values for three-phase are lower than single-phase because current returns via three conductors. For example, a 50mm² copper cable has 0.93 mV/A/m (three-phase) vs 1.55 mV/A/m (single-phase). A 200A load over 80m on 50mm² at 400V gives: (0.93 × 200 × 80) ÷ (1000 × 400) × 100 = 3.72%. That uses most of a 5% total budget in the feeder alone, so upsizing to 70mm² is usually worthwhile.

What are the standard cable sizes in mm² used in UAE?

The standard copper cable sizes per IEC 60228 used in UAE projects are: 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, and 300 mm². For final circuits, 2.5mm² (lighting) and 4mm² (power sockets) are most common. Sub-mains typically range from 16–70mm², and main feeders from 95–300mm². For loads exceeding 300mm² capacity, parallel cables are used. DEWA and ADDC accept both single-core and multi-core configurations.

What is the difference between PVC and XLPE cable insulation?

PVC (polyvinyl chloride) insulation is rated to 70°C conductor temperature, while XLPE (cross-linked polyethylene) is rated to 90°C. In the published rating tables XLPE cables carry more current than PVC cables of the same cross-section, and their rating falls less at high ambient temperature. This calculator uses the same base current table for both and applies a different temperature derating, so take final ratings from the manufacturer's data and the governing standard. XLPE also has better resistance to moisture, chemicals, and ageing — making it preferred for underground installations, outdoor cable trays, and Gulf climate conditions where higher ambient temperatures reduce PVC cable ratings more severely.

Do DEWA and ADDC have different cable sizing requirements?

Both DEWA (Dubai) and ADDC (Abu Dhabi) follow IEC 60364 as the base standard, but have local variations. Voltage drop limits, conductor material rules and approved installation methods can differ between the two authorities and between editions of their regulations, so take the limits from the current DEWA or ADDC/ADWEA regulations and the project specification rather than from this page. Cable colour coding follows the IEC convention: brown/black/grey for phases, blue for neutral, green-yellow for earth. Always verify current edition of the relevant authority's regulations as requirements are updated periodically.

Last Updated: January 2026

Standards Reference: Calculations based on IEC 60364 and BS 7671 (IET Wiring Regulations)

Do this inside Arkan

A calculator gives you one number. Arkan keeps the quantities, inspections and payment requests for the whole project in one place, in English and Arabic.

Arkan screen: inspections

Need More Than Calculators?

Arkan brings all your construction management together: BOQ tracking, payment certificates, document management, scheduling, and more. All integrated. All in one place.

We Value Your Privacy

We use cookies to enhance your browsing experience, analyze site traffic, and personalize content. By clicking "Accept All", you consent to our use of cookies. Read our Privacy Policy

If you allow Marketing Cookies, OpenAI Ads measures accepted demo requests and relates them to advertising using browser and page signals. When enabled, automatic matching may use hashed contact details. You can withdraw permission in Cookie settings. Your enquiry will still be sent if you reject marketing cookies.